Choose a different country or region to see the content specific to your location
Current Region:
United Kingdom (EN)
This site uses some unobtrusive cookies to store information on your computer. By using the website, you hereby agree on cookies storage.
OK
Cookie Policy
How can we help you?
HG & HGEN Series Refrigerated Air Dryers Improve Productivity Simple Reliable
When we streamlined our HG & HGEN Series non-cycling refrigerated compressed air dryers, our engineers focused on simplicity and reliability. Your input helped build a solution that offers the right combination of technology and simplicity to keep your air system at a dry, 38°F (+3°C) pressure dew point, from 5 through 1200 scfm. These dryers are built for durability, in a space-saving design. Sturdy sheet steel is formed and protected by an epoxy-based powdercoat finish. Plus, Deltech’s industry leading, five year warranty is now available for the HGEN Series.
MODEL1 | FLOW RATE SCFM2 |
FLOW RATE M3/H |
REFRIGERANT | VOLTAGE | POWER KW |
INLET/OUTLET CONNECTIONS |
---|---|---|---|---|---|---|
HG5-10 | 5 | 17 | R 134a | 115/1/60 | 0.2 | 3/8" OD |
HG15 | 15 | 25 | R 134a | 115/1/60 | 0.24 | 3/8" OD |
HG25 | 25 | 42 | R 134a | 115/1/60 | 0.41 | 3/4" NPT |
HG35 | 35 | 59 | R 134a | 115/1/60 | 0.46 | 3/4" NPT |
HG50 | 50 | 85 | R 134a | 115/1/60 | 0.57 | 3/4" NPT |
HGEN75 | 75 | 127 | R 134a | 115/1/60 | 0.52 | 1" NPT |
HGEN100 | 100 | 170 | R 134a | 115/1/60 | 0.65 | 1" NPT |
HGEN125 | 125 | 212 | R 134a | 115/1/60 | 0.68 | 1" NPT |
HGEN150-1 | 150 | 255 | R 407c | 115/1/60 | 0.91 | 1" NPT |
HGEN200-4 | 200 | 340 | R 407c | 460/3/60 | 1.81 | 1" NPT |
HGEN250-4 | 250 | 425 | R 407c | 460/3/60 | 1.92 | 2" NPT |
HGEN300-4 | 300 | 510 | R 407c | 460/3/60 | 2.48 | 2" NPT |
HGEN400-4 | 400 | 680 | R 407c | 460/3/60 | 3.09 | 2" NPT |
HGEN500-4 | 500 | 850 | R 407c | 460/3/60 | 3.18 | 2" NPT |
HGEN6003 | 600 | 1,020 | R 407c | 460/3/60 | 3.8 | 2" NPT |
HGEN8003 | 800 | 1,360 | R 407c | 460/3/60 | 5.4 | 3" FLG |
HGEN10003 | 1,000 | 1,700 | R 407c | 460/3/60 | 6.6 | 4" FLG |
HGEN12003 | 1,200 | 2,040 | R 407c | 460/3/60 | 8.7 | 4" FLG |
1 1 = For Filter Pack model, add “-FP” to standard model number. (Example: HGEN75-FP)
Dimensions, weights, and inlet/outlet connections are dryer only and do not include filtration.
Filtration package shipped loose, additional fittings may be required.
2 Rated Flow Capacity – Conditions for rating dryers are in accordance with ISO 7183 (Option A2). Compressed air at dryer inlet: 100 psig (6.7 barg) and 100˚F (38˚C); ambient air temperature: 100˚F (38˚C); operating on 60 Hz power supply.
3 Available in water cooled
At rated conditions, pressure drop is less than 5 psig.
MODEL1 | DIMENSIONS (INCHES) | WEIGHT LBS |
||
---|---|---|---|---|
H | W | D | ||
HG5-10 | 15 | 13 | 13 | 64 |
1 1 = For Filter Pack model, add “-FP” to standard model number. (Example: HGEN75-FP)
Dimensions, weights, and inlet/outlet connections are dryer only and do not include filtration.
Filtration package shipped loose, additional fittings may be required.
2 Rated Flow Capacity – Conditions for rating dryers are in accordance with ISO 7183 (Option A2). Compressed air at dryer inlet: 100 psig (6.7 barg) and 100˚F (38˚C); ambient air temperature: 100˚F (38˚C); operating on 60 Hz power supply.
MODEL1 | DIMENSIONS (INCHES) | WEIGHT LBS |
||
---|---|---|---|---|
H | W | D | ||
HG15 | 15 | 13 | 13 | 69 |
1 1 = For Filter Pack model, add “-FP” to standard model number. (Example: HGEN75-FP)
Dimensions, weights, and inlet/outlet connections are dryer only and do not include filtration.
Filtration package shipped loose, additional fittings may be required.
2 Rated Flow Capacity – Conditions for rating dryers are in accordance with ISO 7183 (Option A2). Compressed air at dryer inlet: 100 psig (6.7 barg) and 100˚F (38˚C); ambient air temperature: 100˚F (38˚C); operating on 60 Hz power supply.
MODEL1 | DIMENSIONS (INCHES) | WEIGHT LBS |
||
---|---|---|---|---|
H | W | D | ||
HG25 | 22 | 16 | 15 | 88 |
1 1 = For Filter Pack model, add “-FP” to standard model number. (Example: HGEN75-FP)
Dimensions, weights, and inlet/outlet connections are dryer only and do not include filtration.
Filtration package shipped loose, additional fittings may be required.
2 Rated Flow Capacity – Conditions for rating dryers are in accordance with ISO 7183 (Option A2). Compressed air at dryer inlet: 100 psig (6.7 barg) and 100˚F (38˚C); ambient air temperature: 100˚F (38˚C); operating on 60 Hz power supply.
FLOW MODEL |
MAX INLET AIR PRESSURE |
MIN INLET AIR PRESSURE |
MAX INLET AIR TEMPERATURE |
MIN INLET AIR TEMPERATURE |
MAX AMBIENT AIR TEMPERATURE |
MIN AMBIENT AIR TEMPERATURE |
||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
SCFM | PSIG | BARG | PSIG | BARG | ˚F | ˚C | ˚F | ˚C | ˚F | ˚C | ˚F | ˚C |
5-10 to 50 | 250 | 17 | 30 | 2 | 120 | 49 | 40 | 4 | 110 | 43 | 45 | 7 |
75 to 500 | 232 | 16 | 43 | 3 | 120 | 49 | 45 | 7 | 110 | 43 | 37 | 3 |
600-1200 | 232 | 16 | 43 | 3 | 120 | 49 | 45 | 7 | 110 | 43 | 34 | 1 |