FLEX Series - Refrigerated Air Dryers 75 to 2000 scfm

DRYERS - COMPRESSED AIR / REFRIGERATED COMPRESSED AIR DRYERS

FLEX Series Sustainable Energy Saving Solution

Energy Saving Sustainability

The FLEX Series lowers air system power costs and improves productivity by matching power consumption to compressed air demand.

In a typical manufacturing facility, up to 30% of electricity consumed is for generating and treating compressed air. To reduce total cost of operation and qualify for utility company incentive programs, proper air treatment equipment selection and application is required.

Load Matching Performance

Compressed air load profiles in most manufacturing facilities fluctuate. The FLEX Series provides cost-effective energy savings by matching electrical power consumed in direct proportion to air demand. Linear load matching is achieved from 0% up to 100% demand.

Non-cycling dryers operate with the refrigeration compressor running continuously, regardless of inlet load conditions. Minimal energy savings are realized from 100% down to 0% inlet air load.

Linear Energy Savings

FLEX Series dryers automatically cycle (on /off) the refrigeration compressor in response to inlet load conditions. As the inlet air load is reduced, the power requirement to dry the air is matched in proportion to the demand. For example, at 60% inlet air load, a non-cycling dryer consumes 96% of the full load power consumption, a 4% energy savings. By comparison, at 60% inlet air load, the FLEX Series consumes only 60% of the full load power, a 40% energy savings.

How It Works

  1.  The FLEX Series utilizes a phase change (PCM) heat transfer medium between the refrigeration and compressed air circuits that serves as a reservoir for thermal storage. 

  2. The thermal reservoir is comprised of a 3-in-1 heat exchanger (patent pending) filled with a phase change material that efficiently transfers heat energy through a “change of state”.

    Phase Change: changing from liquid to solid back to liquid in a continuous cycle

  3. The refrigeration circuit operates to cool down the PCM until it forms into a solid at which time the refrigeration system cycles off. 

  4. As the compressed air enters the PCM to air section of the heat exchanger, the PCM media absorbs heat for the airstream and begins to melt the PCM media at a constant temperature. 

  5. When most of the PCM media has turned to liquid the refrigeration system cycles on to again cool down the PCM media turning it back into a solid. 

  6. This cycle repeats as required to meet the corresponding compressed air load on the FLEX dryer. 
flex-series-flow.jpg

FLEX Series Models for North America

Dryer
Model
Inlet FlowPressure DropVoltagesInlet/Outlet
Connections
Operating Power
SCFMNM3/HPSIINKW
DFX 1.1751272.9115/1/60NPT 1"0.54
DFX 1.21001703.0115/1/60NPT 1"0.62
DFX 1.5-11502553.6115/1/60NPT 2"1.04
DFX 2.1-42003402.2460/3/60NPT 2"1.26
DFX 3.13005093.6460/3/60NPT 2"1.99
DFX 4.54507653.0460/3/60NPT 2"3.23
DFX 5.55509353.0460/3/60NPT 2"3.42
DFX 8.180013003.7460/3/60FLG 3"4.30
DFX 10.1100017005.0460/3/60FLG 3"5.84
DFX 12.5125021504.6460/3/60FLG 4"7.60
DFX 15.1150025503.9460/3/60FLG 4"9.00
DFX 20.1200034003.1460/3/60FLG 4"10.00
Performance data presented in accordance with ISO 7183 (Option A2) conditions: 100°F inlet temperature, 100°F ambient temperature and 100 psig conditions.



FLEX Series Models for EMEA

Dryer
Model
Inlet FlowPressure DropVoltagesInlet/Outlet
Connections
Operating Power
SCFMM3/HBARINKW
DFX 1.1751270.20230/1/50 1"0.43
DFX 1.21001700.21230/1/50 1"0.43
DFX 1.51502550.25230/1/50 2"0.59
DFX 2.12003400.15230/1/50 2"0.85
DFX 3.13005090.25230/1/50 2"1.30
DFX 4.14006800.17230/1/50 2"1.66
DFX 5.55509350.20230/1/50 2"2.00

Flex Series Models

Dryer
Model
DimensionsApprox
Weight
HWD
INMMINMMINMMLBKG
DFX 1.130751143632460312054.5
 Performance data presented in accordance with ISO 7183 (Option A2) conditions: 100°F inlet temperature, 100°F ambient temperature and 100 psig conditions.

Flex Series Models

Dryer
Model
DimensionsApprox
Weight
HWD
INMMINMMINMMLBKG
DFX 1.228711143633178114766.5
 Performance data presented in accordance with ISO 7183 (Option A2) conditions: 100°F inlet temperature, 100°F ambient temperature and 100 psig conditions.

Flex Series Models

Dryer
Model
DimensionsApprox
Weight
HWD
INMMINMMINMMLBKG
DFX 1.5-130761184433690120392
 Performance data presented in accordance with ISO 7183 (Option A2) conditions: 100°F inlet temperature, 100°F ambient temperature and 100 psig conditions.

Flex Series Models

Dryer
Model
DimensionsApprox
Weight
HWD
INMMINMMINMMLBKG
DFX 2.1-4307611844338961244111
 Performance data presented in accordance with ISO 7183 (Option A2) conditions: 100°F inlet temperature, 100°F ambient temperature and 100 psig conditions.

Flex Series Models

Dryer
Model
DimensionsApprox
Weight
HWD
INMMINMMINMMLBKG
DFX 3.13691119493441111324147
 Performance data presented in accordance with ISO 7183 (Option A2) conditions: 100°F inlet temperature, 100°F ambient temperature and 100 psig conditions.

Flex Series Models

Dryer
Model
DimensionsApprox
Weight
HWD
INMMINMMINMMLBKG
DFX 4.541103220494491253366166
 Performance data presented in accordance with ISO 7183 (Option A2) conditions: 100°F inlet temperature, 100°F ambient temperature and 100 psig conditions.

Flex Series Models

Dryer
Model
DimensionsApprox
Weight
HWD
INMMINMMINMMLBKG
DFX 5.541103220494491253396180
 Performance data presented in accordance with ISO 7183 (Option A2) conditions: 100°F inlet temperature, 100°F ambient temperature and 100 psig conditions.

Flex Series Models

Dryer
Model
DimensionsApprox
Weight
HWD
INMMINMMINMMLBKG
DFX 8.1591488328005914941056479
 Performance data presented in accordance with ISO 7183 (Option A2) conditions: 100°F inlet temperature, 100°F ambient temperature and 100 psig conditions.

Flex Series Models

Dryer
Model
DimensionsApprox
Weight
HWD
INMMINMMINMMLBKG
DFX 10.1591488348506215721211549
 Performance data presented in accordance with ISO 7183 (Option A2) conditions: 100°F inlet temperature, 100°F ambient temperature and 100 psig conditions.

Flex Series Models

Dryer
Model
DimensionsApprox
Weight
HWD
INMMINMMINMMLBKG
DFX 12.55914883910006215721537697
 Performance data presented in accordance with ISO 7183 (Option A2) conditions: 100°F inlet temperature, 100°F ambient temperature and 100 psig conditions.

North America DFX 1.1

Flex Series Models

Dryer
Model
DimensionsApprox
Weight
HWD
INMMINMMINMMLBKG
DFX 1.130751143632460312054.5
 Performance data presented in accordance with ISO 7183 (Option A2) conditions: 100°F inlet temperature, 100°F ambient temperature and 100 psig conditions.

North America DFX 1.2

Flex Series Models

Dryer
Model
DimensionsApprox
Weight
HWD
INMMINMMINMMLBKG
DFX 1.228711143633178114766.5
 Performance data presented in accordance with ISO 7183 (Option A2) conditions: 100°F inlet temperature, 100°F ambient temperature and 100 psig conditions.

North America DFX 1.5-1

Flex Series Models

Dryer
Model
DimensionsApprox
Weight
HWD
INMMINMMINMMLBKG
DFX 1.5-130761184433690120392
 Performance data presented in accordance with ISO 7183 (Option A2) conditions: 100°F inlet temperature, 100°F ambient temperature and 100 psig conditions.

North America DFX 2.1-4

Flex Series Models

Dryer
Model
DimensionsApprox
Weight
HWD
INMMINMMINMMLBKG
DFX 2.1-4307611844338961244111
 Performance data presented in accordance with ISO 7183 (Option A2) conditions: 100°F inlet temperature, 100°F ambient temperature and 100 psig conditions.

North America DFX 3.1

Flex Series Models

Dryer
Model
DimensionsApprox
Weight
HWD
INMMINMMINMMLBKG
DFX 3.13691119493441111324147
 Performance data presented in accordance with ISO 7183 (Option A2) conditions: 100°F inlet temperature, 100°F ambient temperature and 100 psig conditions.

North America DFX 4.5

Flex Series Models

Dryer
Model
DimensionsApprox
Weight
HWD
INMMINMMINMMLBKG
DFX 4.541103220494491253366166
 Performance data presented in accordance with ISO 7183 (Option A2) conditions: 100°F inlet temperature, 100°F ambient temperature and 100 psig conditions.

North America DFX 5.5

Flex Series Models

Dryer
Model
DimensionsApprox
Weight
HWD
INMMINMMINMMLBKG
DFX 5.541103220494491253396180
 Performance data presented in accordance with ISO 7183 (Option A2) conditions: 100°F inlet temperature, 100°F ambient temperature and 100 psig conditions.

North America DFX 8.1

Flex Series Models

Dryer
Model
DimensionsApprox
Weight
HWD
INMMINMMINMMLBKG
DFX 8.1591488328005914941056479
 Performance data presented in accordance with ISO 7183 (Option A2) conditions: 100°F inlet temperature, 100°F ambient temperature and 100 psig conditions.

North America DFX 10.1

Flex Series Models

Dryer
Model
DimensionsApprox
Weight
HWD
INMMINMMINMMLBKG
DFX 10.1591488348506215721211549
 Performance data presented in accordance with ISO 7183 (Option A2) conditions: 100°F inlet temperature, 100°F ambient temperature and 100 psig conditions.

North America DFX 12.5

Flex Series Models

Dryer
Model
DimensionsApprox
Weight
HWD
INMMINMMINMMLBKG
DFX 12.55914883910006215721537697
 Performance data presented in accordance with ISO 7183 (Option A2) conditions: 100°F inlet temperature, 100°F ambient temperature and 100 psig conditions.

Features

Energy Saving Sustainability

The FLEX Series lowers air system power costs and improves productivity by matching power consumption to compressed air demand.

In a typical manufacturing facility, up to 30% of electricity consumed is for generating and treating compressed air. To reduce total cost of operation and qualify for utility company incentive programs, proper air treatment equipment selection and application is required.

Load Matching Performance

Compressed air load profiles in most manufacturing facilities fluctuate. The FLEX Series provides cost-effective energy savings by matching electrical power consumed in direct proportion to air demand. Linear load matching is achieved from 0% up to 100% demand.

Non-cycling dryers operate with the refrigeration compressor running continuously, regardless of inlet load conditions. Minimal energy savings are realized from 100% down to 0% inlet air load.

Linear Energy Savings

FLEX Series dryers automatically cycle (on /off) the refrigeration compressor in response to inlet load conditions. As the inlet air load is reduced, the power requirement to dry the air is matched in proportion to the demand. For example, at 60% inlet air load, a non-cycling dryer consumes 96% of the full load power consumption, a 4% energy savings. By comparison, at 60% inlet air load, the FLEX Series consumes only 60% of the full load power, a 40% energy savings.

Theory of Operation

How It Works

  1.  The FLEX Series utilizes a phase change (PCM) heat transfer medium between the refrigeration and compressed air circuits that serves as a reservoir for thermal storage. 

  2. The thermal reservoir is comprised of a 3-in-1 heat exchanger (patent pending) filled with a phase change material that efficiently transfers heat energy through a “change of state”.

    Phase Change: changing from liquid to solid back to liquid in a continuous cycle

  3. The refrigeration circuit operates to cool down the PCM until it forms into a solid at which time the refrigeration system cycles off. 

  4. As the compressed air enters the PCM to air section of the heat exchanger, the PCM media absorbs heat for the airstream and begins to melt the PCM media at a constant temperature. 

  5. When most of the PCM media has turned to liquid the refrigeration system cycles on to again cool down the PCM media turning it back into a solid. 

  6. This cycle repeats as required to meet the corresponding compressed air load on the FLEX dryer. 
flex-series-flow.jpg

Specifications

FLEX Series Models for North America

Dryer
Model
Inlet FlowPressure DropVoltagesInlet/Outlet
Connections
Operating Power
SCFMNM3/HPSIINKW
DFX 1.1751272.9115/1/60NPT 1"0.54
DFX 1.21001703.0115/1/60NPT 1"0.62
DFX 1.5-11502553.6115/1/60NPT 2"1.04
DFX 2.1-42003402.2460/3/60NPT 2"1.26
DFX 3.13005093.6460/3/60NPT 2"1.99
DFX 4.54507653.0460/3/60NPT 2"3.23
DFX 5.55509353.0460/3/60NPT 2"3.42
DFX 8.180013003.7460/3/60FLG 3"4.30
DFX 10.1100017005.0460/3/60FLG 3"5.84
DFX 12.5125021504.6460/3/60FLG 4"7.60
DFX 15.1150025503.9460/3/60FLG 4"9.00
DFX 20.1200034003.1460/3/60FLG 4"10.00
Performance data presented in accordance with ISO 7183 (Option A2) conditions: 100°F inlet temperature, 100°F ambient temperature and 100 psig conditions.



FLEX Series Models for EMEA

Dryer
Model
Inlet FlowPressure DropVoltagesInlet/Outlet
Connections
Operating Power
SCFMM3/HBARINKW
DFX 1.1751270.20230/1/50 1"0.43
DFX 1.21001700.21230/1/50 1"0.43
DFX 1.51502550.25230/1/50 2"0.59
DFX 2.12003400.15230/1/50 2"0.85
DFX 3.13005090.25230/1/50 2"1.30
DFX 4.14006800.17230/1/50 2"1.66
DFX 5.55509350.20230/1/50 2"2.00

Dimensions

Flex Series Models

Dryer
Model
DimensionsApprox
Weight
HWD
INMMINMMINMMLBKG
DFX 1.130751143632460312054.5
 Performance data presented in accordance with ISO 7183 (Option A2) conditions: 100°F inlet temperature, 100°F ambient temperature and 100 psig conditions.

Flex Series Models

Dryer
Model
DimensionsApprox
Weight
HWD
INMMINMMINMMLBKG
DFX 1.228711143633178114766.5
 Performance data presented in accordance with ISO 7183 (Option A2) conditions: 100°F inlet temperature, 100°F ambient temperature and 100 psig conditions.

Flex Series Models

Dryer
Model
DimensionsApprox
Weight
HWD
INMMINMMINMMLBKG
DFX 1.5-130761184433690120392
 Performance data presented in accordance with ISO 7183 (Option A2) conditions: 100°F inlet temperature, 100°F ambient temperature and 100 psig conditions.

Flex Series Models

Dryer
Model
DimensionsApprox
Weight
HWD
INMMINMMINMMLBKG
DFX 2.1-4307611844338961244111
 Performance data presented in accordance with ISO 7183 (Option A2) conditions: 100°F inlet temperature, 100°F ambient temperature and 100 psig conditions.

Flex Series Models

Dryer
Model
DimensionsApprox
Weight
HWD
INMMINMMINMMLBKG
DFX 3.13691119493441111324147
 Performance data presented in accordance with ISO 7183 (Option A2) conditions: 100°F inlet temperature, 100°F ambient temperature and 100 psig conditions.

Flex Series Models

Dryer
Model
DimensionsApprox
Weight
HWD
INMMINMMINMMLBKG
DFX 4.541103220494491253366166
 Performance data presented in accordance with ISO 7183 (Option A2) conditions: 100°F inlet temperature, 100°F ambient temperature and 100 psig conditions.

Flex Series Models

Dryer
Model
DimensionsApprox
Weight
HWD
INMMINMMINMMLBKG
DFX 5.541103220494491253396180
 Performance data presented in accordance with ISO 7183 (Option A2) conditions: 100°F inlet temperature, 100°F ambient temperature and 100 psig conditions.

Flex Series Models

Dryer
Model
DimensionsApprox
Weight
HWD
INMMINMMINMMLBKG
DFX 8.1591488328005914941056479
 Performance data presented in accordance with ISO 7183 (Option A2) conditions: 100°F inlet temperature, 100°F ambient temperature and 100 psig conditions.

Flex Series Models

Dryer
Model
DimensionsApprox
Weight
HWD
INMMINMMINMMLBKG
DFX 10.1591488348506215721211549
 Performance data presented in accordance with ISO 7183 (Option A2) conditions: 100°F inlet temperature, 100°F ambient temperature and 100 psig conditions.

Flex Series Models

Dryer
Model
DimensionsApprox
Weight
HWD
INMMINMMINMMLBKG
DFX 12.55914883910006215721537697
 Performance data presented in accordance with ISO 7183 (Option A2) conditions: 100°F inlet temperature, 100°F ambient temperature and 100 psig conditions.

North America DFX 1.1

Flex Series Models

Dryer
Model
DimensionsApprox
Weight
HWD
INMMINMMINMMLBKG
DFX 1.130751143632460312054.5
 Performance data presented in accordance with ISO 7183 (Option A2) conditions: 100°F inlet temperature, 100°F ambient temperature and 100 psig conditions.

North America DFX 1.2

Flex Series Models

Dryer
Model
DimensionsApprox
Weight
HWD
INMMINMMINMMLBKG
DFX 1.228711143633178114766.5
 Performance data presented in accordance with ISO 7183 (Option A2) conditions: 100°F inlet temperature, 100°F ambient temperature and 100 psig conditions.

North America DFX 1.5-1

Flex Series Models

Dryer
Model
DimensionsApprox
Weight
HWD
INMMINMMINMMLBKG
DFX 1.5-130761184433690120392
 Performance data presented in accordance with ISO 7183 (Option A2) conditions: 100°F inlet temperature, 100°F ambient temperature and 100 psig conditions.

North America DFX 2.1-4

Flex Series Models

Dryer
Model
DimensionsApprox
Weight
HWD
INMMINMMINMMLBKG
DFX 2.1-4307611844338961244111
 Performance data presented in accordance with ISO 7183 (Option A2) conditions: 100°F inlet temperature, 100°F ambient temperature and 100 psig conditions.

North America DFX 3.1

Flex Series Models

Dryer
Model
DimensionsApprox
Weight
HWD
INMMINMMINMMLBKG
DFX 3.13691119493441111324147
 Performance data presented in accordance with ISO 7183 (Option A2) conditions: 100°F inlet temperature, 100°F ambient temperature and 100 psig conditions.

North America DFX 4.5

Flex Series Models

Dryer
Model
DimensionsApprox
Weight
HWD
INMMINMMINMMLBKG
DFX 4.541103220494491253366166
 Performance data presented in accordance with ISO 7183 (Option A2) conditions: 100°F inlet temperature, 100°F ambient temperature and 100 psig conditions.

North America DFX 5.5

Flex Series Models

Dryer
Model
DimensionsApprox
Weight
HWD
INMMINMMINMMLBKG
DFX 5.541103220494491253396180
 Performance data presented in accordance with ISO 7183 (Option A2) conditions: 100°F inlet temperature, 100°F ambient temperature and 100 psig conditions.

North America DFX 8.1

Flex Series Models

Dryer
Model
DimensionsApprox
Weight
HWD
INMMINMMINMMLBKG
DFX 8.1591488328005914941056479
 Performance data presented in accordance with ISO 7183 (Option A2) conditions: 100°F inlet temperature, 100°F ambient temperature and 100 psig conditions.

North America DFX 10.1

Flex Series Models

Dryer
Model
DimensionsApprox
Weight
HWD
INMMINMMINMMLBKG
DFX 10.1591488348506215721211549
 Performance data presented in accordance with ISO 7183 (Option A2) conditions: 100°F inlet temperature, 100°F ambient temperature and 100 psig conditions.

North America DFX 12.5

Flex Series Models

Dryer
Model
DimensionsApprox
Weight
HWD
INMMINMMINMMLBKG
DFX 12.55914883910006215721537697
 Performance data presented in accordance with ISO 7183 (Option A2) conditions: 100°F inlet temperature, 100°F ambient temperature and 100 psig conditions.